450 meters east from the Shijialiancheng Village Committee in Shaozhuang Township, Suning County, Cangzhou City, Hebei Province, on the north side of the road
imgi_6_1
X
ZW20-12F High Voltage Substations Industrial Vaccum Interrupter Circuit Breaker Load Break Switch
ZW20-12F Vacuum circuit breakers are essential components in electrical systems, providing reliable protection against overcurrents and short circuits. These devices are designed to interrupt current flow in a circuit by creating a vacuum between the contacts, ensuring efficient and safe operation. With their compact size and high breaking capacity, vacuum circuit breakers are ideal for a wide range of applications, from residential to industrial settings. It is important to regularly inspect and maintain these breakers to ensure they continue to function properly and protect the electrical system. By understanding the key features and benefits of vacuum circuit breakers, users can make informed decisions when selecting and using these critical components.
Product Advantage
1. One of the main advantages of ZW20-12F vacuum circuit breakers is their high reliability. Due to the absence of any medium for arc extinction, vacuum circuit breakers are able to interrupt current quickly and effectively, reducing the risk of electrical faults and ensuring a stable power supply..
2. The key advantage of ZW20-12F vacuum circuit breakers is their compact size and lightweight design. This makes them easy to install and maintain, saving both time and resources for users.
3. ZW20-12F vacuum circuit breakers are environmentally friendly, as they do not use any harmful substances in their operation, reducing the impact on the environment.
4. Overall, the advantages of ZW20-12F vacuum circuit breakers make them a reliable, efficient, and sustainable choice for various electrical applications.
Technical Parameters
No.
Item
Unit
Data
1
Rated frequency
Hz
50
2
Rated voltage
kV
12
3
Rated current
A
630
1250
4
Rated short-time power frequency withstand voltage
Interphase, to earth(wet)
kV/min
34/1
Interphase, to earth(dry)
42/1
Fracture (dry)
48/1
Secondary circuit to earth
2/1
5
Rated lightning impulse withstand voltage
Interphase, to earth
kV
75
Fracture
85
6
Rated short-circuit breaking current
kA
20/25
7
Rated short-circuit making current(peak)
50/63
8
Rated short-time withstand current and duration
kA/s
(20/25)/4
9
Rated peak withstand current
kA
50/63
10
Rated short-circuit breaking current breaking times
Times
30 (E2 Level)
11
Gas Rated Gauge Pressure
MPa
0
12
Main circuit resistance
μΩ
≤120
13
Rated Operating Voltage and Rated Voltage for auxiliary(control) circuit
V
AC/DC220,DC48,DC24
14
Mechanical life
Times
10000 (M2 level)
Note: If the altitude is over 1000m, the rated insulation level should be modified as appropriate.
USAGE
USAGE: ENVIRONMENTAL CONDITION
1. Altitude: ≤ 3000m, If the altitude is higher than 3000m, the rated insulation level shall be corrected accordingly.
2. Ambient temperature: -30oC ~ +65oC
3. Wind Speed: 34m/s
4. Wind pressure: 700Pa
5. Pollution level: IV level
6. Icing thickness: Not more than 10mm
7. Storage Temperature: -40oC ~ +85oC
Outline and Dimension
450 meters east from the Shijialiancheng Village Committee in Shaozhuang Township, Suning County, Cangzhou City, Hebei Province, on the north side of the road