    HXGN-12 SF6 Gas Insulated Electrical Medium Voltage Ring Mian Unit

    Categories:

    Contact Now
    HXGN  – 12 box type fixed AC metal-enclosed ring network switchgear (hereinafter referred to as “ring network cabinet/switchgear”) is suitable for power distribution systems in areas such as industrial and mining enterprises, residential areas, high-rise buildings, schools, and parks. It is used as an indoor AC three-phase 12kV, 50Hz ring network power supply unit and terminal power distribution equipment. It can disconnect or close the rated load current and transformer no-load current and can disconnect or close the overhead line, cable line, or capacitive current at a certain distance. The load switch fuse combination cabinet can disconnect the rated short-circuit current at one time. In the power system, as the protection of distribution equipment and the distribution and control of electric energy, it has a perfect “five prevention” locking function. Product Advantage 1. The characteristics and advantages of the sulfur hexafluoride SF6 ring main unit are worth considering when looking for a reliable and efficient solution for power distribution. This type of equipment is known for its high level of insulation, which ensures the safety and reliability of the electrical system. 2. Additionally, the sulfur hexafluoride SF6 ring main unit is compact in size, making it easy to install and maintain in various settings. Its modular design allows for flexibility and scalability, enabling users to customize the unit according to their specific needs. 3. Furthermore, the sulfur hexafluoride SF6  ring main unit is environmentally friendly, as it is designed to minimize greenhouse gas emissions and reduce the overall carbon footprint of the electrical system. 4. Overall, this type of SF6  ring main unit equipment offers a cost-effective and sustainable solution for power distribution, making it a popular choice among industries and utilities. Technical Parameters
    No. Item Unit Parameters
    1 Rated voltage kV 7.2 / 12
    2 Rated Current of Main Bus A 630
    3 Rated Current Incoming Cabinet A 630
    Outgoing Cabinet (Combined Electrical Cabinet) A 125 (Biggest)
    4 Rated Short-Time Withstand Current kA 20
    5 Rated Peak Withstand Current kA 31.5
    6 Rated Short-Time Making Current (Peak Value) kA 50
    7 Rated Active Load Breaking Current A 630
    8 Rated Closed-Loop Breaking Current A 630
    9 Rated Cable Charging Current A 10
    10 Rated Short-Time Withstand Current of Earthing Switch kA 20
    11 Rated Peak Withstand Current of Earthing Switch kA 50
    12 Rated Short-Time Making Current Making Peak Value of Earthing Switch. kA 50
    13 Rated Breaking Current of Cable Point A 3150
    14 1min Power Frequency Withstand Voltage Phase-Phase Vacuum Fracture kV 42
    Isolation Fracture 48
    15 Lightning Impulse Withstand Voltage Phase-Phase Vacuum Fracture kV 75
    Isolation Fracture 85
    16 Mechanical Life Span Vacuum Load Switch Times 10000
    Isolation knife Earth Knife 2000
    17 Load Switch Average Closing Speed m/s 0.6±0.2
    Average Opening Speed 1.1±0.2
    3-Phase Asynchrony ≤2
    18 Fuse for the Combined Appliance Maximum Rated Current A 125
    Rated Short-Circuit Breaking Current kA 31.5
    19 Protection Level IP3X
    Usage: Environmental Condition 1. The altitude shall not exceed 1000 meters, and the altitude under special use conditions shall not exceed 2000 meters 2. Ambient Temp: Upper limit +40˚C, The average value measured within 24h shall not exceed 35˚C, and the lowest ambient air temp -15˚C 3. Relative humidity: The Ave. value of relative humidity measured within 24h shall not exceed 95% The average value of water vapor pressure measured within 24h shall not exceed 2.2kpa The average monthly relative temperature shall not exceed 90% The average monthly water vapor pressure shall not exceed 1.8kpa 4. The surrounding air is not appreciably polluted by dust, smoke, corrosive and/or flammable gases, vapors, or salt mist. 5. When the equipment is installed, the inclination from the vertical plane should not exceed 5˚C. 6. The equipment should be installed in a place free from severe pulling and impact. 7. Note: Users can negotiate with our company for special requirements. Outline and Dimension Model No.&Definition

    Request Inquery

    Request a Quote

    Contact Us

  • Hebei Shiyue Electrical Equipment Co., Ltd.
  • +86 15369772778240164684@qq.com
  • 450 meters east from the Shijialiancheng Village Committee in Shaozhuang Township, Suning County, Cangzhou City, Hebei Province, on the north side of the road
  • Copyright © 2026 Hebei Shiyue Electrical Equipment Co., Ltd. All Rights Reserved.

    Contact Us
    whatsapp

    Request Inquery